Device-specific Limits
Description
Maximum number of synchronous
changes of chart inputs per task level
Maximum number of chart outputs per
task level
Additional Limits
Task Level
MW_BEARB
PLC1_BEARB
PLC_BEARB
SFS_BEARB
1)
When the limit is exceeded, an error message is output by the device. Consequently, the device starts mon-
itoring. The red ERROR-LED lights up.
2)
The following condition applies for the maximum number of timers: (2 · number of TIMER + number of
TIMER_SHORT) < 30. TIMER and TIMER_SHORT hence share the available timer resources within the
frame of this inequation. The limit does not apply to the LONG_TIMER.
3)
The time values for the blocks TIMER and TIMER_SHORT must not be selected shorter than the time res-
olution of the device, as the blocks will not then start with the starting pulse.
Maximum Number of TICKS in the Task Levels
MW_BEARB (Measured Value Processing )
PLC1_BEARB (Slow PLC Processing )
PLC_BEARB (Fast PLC Processing )
SFS_BEARB (Interlocking )
1)
When the sum of TICKS of all blocks exceeds the limits before-mentioned, an error message is output by
CFC.
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
Limit
165
When the limit is exceeded, an error message is output by
the device. Consequently, the device starts monitoring. The
red ERROR-LED lights up.
150
1)
Additional limits
for the following CFC blocks:
Maximum Number of Modules in the Task Levels
2) 3)
TIMER
15
Task Level
4.24 User-defined Functions (CFC)
Comments
2) 3)
TIMER_SHORT
30
Technical Data
1)
Limit in TICKS
10000
4000
400
10000
529