Multi-functional protective relay with local control
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Appendix
A.8 Settings
Addr.
Parameter
1202
50-2 PICKUP
1203
50-2 DELAY
1204
50-1 PICKUP
1205
50-1 DELAY
1207
51 PICKUP
1208
51 TIME DIAL
1209
51 TIME DIAL
1210
51 Drop-out
1211
51 IEC CURVE
1212
51 ANSI CURVE
1213A
MANUAL CLOSE
1214A
50-2 active
1215A
50 T DROP-OUT
1216A
50-3 active
1217
50-3 PICKUP
1218
50-3 DELAY
1219A
50-3 measurem.
1220A
50-2 measurem.
1221A
50-1 measurem.
1222A
51 measurem.
1223
VOLT. INFLUENCE
1224
51V V<
1230
51/51N
1231
MofPU Res T/Tp
1301
FCT 50N/51N
1302
50N-2 PICKUP
1303
50N-2 DELAY
1304
50N-1 PICKUP
1305
50N-1 DELAY
1307
51N PICKUP
632
Function
C
Setting Options
0.10 .. 35.00 A; ∞
50/51 Overcur.
1A
0.50 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
50/51 Overcur.
0.10 .. 35.00 A; ∞
50/51 Overcur.
1A
0.50 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
50/51 Overcur.
50/51 Overcur.
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
0.05 .. 3.20 sec; ∞
50/51 Overcur.
0.50 .. 15.00 ; ∞
50/51 Overcur.
50/51 Overcur.
Instantaneous
Disk Emulation
50/51 Overcur.
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
50/51 Overcur.
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
50/51 Overcur.
50-3 instant.
50-2 instant.
50 -1 instant.
51 instant.
Inactive
50/51 Overcur.
Always
with 79 active
50/51 Overcur.
0.00 .. 60.00 sec
50/51 Overcur.
Always
with 79 active
1.00 .. 35.00 A; ∞
50/51 Overcur.
1A
5.00 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
50/51 Overcur.
50/51 Overcur.
Fundamental
True RMS
Instantaneous
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
NO
Volt. controll.
Volt. restraint
50/51 Overcur.
10.0 .. 125.0 V
1.00 .. 20.00 I/Ip; ∞
50/51 Overcur.
0.01 .. 999.00 TD
0.05 .. 0.95 I/Ip; ∞
50/51 Overcur.
0.01 .. 999.00 TD
50/51 Overcur.
ON
OFF
0.05 .. 35.00 A; ∞
50/51 Overcur.
1A
0.25 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
50/51 Overcur.
0.05 .. 35.00 A; ∞
50/51 Overcur.
1A
0.25 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
50/51 Overcur.
50/51 Overcur.
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
Default Setting
2.00 A
50-2 Pickup
10.00 A
0.00 sec
50-2 Time Delay
1.00 A
50-1 Pickup
5.00 A
0.50 sec
50-1 Time Delay
1.00 A
51 Pickup
5.00 A
0.50 sec
51 Time Dial
5.00
51 Time Dial
Disk Emulation
Drop-out characteristic
Normal Inverse
IEC Curve
Very Inverse
ANSI Curve
50-2 instant.
Manual Close Mode
Always
50-2 active
0.00 sec
50 Drop-Out Time Delay
Always
50-3 active
∞ A
50-3 Pickup
∞ A
0.00 sec
50-3 Time Delay
Fundamental
50-3 measurement of
Fundamental
50-2 measurement of
Fundamental
50-1 measurement of
Fundamental
51 measurement of
NO
51V Voltage Influence
75.0 V
51V V< Threshold for Release Ip
51/51N
Multiple of Pickup <-> T/Tp
ON
50N, 51N Ground Time Overcur-
rent
0.50 A
50N-2 Pickup
2.50 A
0.10 sec
50N-2 Time Delay
0.20 A
50N-1 Pickup
1.00 A
0.50 sec
50N-1 Time Delay
0.20 A
51N Pickup
1.00 A
SIPROTEC, 7SJ62/64, Manual