Ground Fault Location

Application Example
Directional determination may often be used to locate ground faults. In radial systems, locating the ground fault
is relatively simple. Since all feeders from a common bus (Figure 2-87) deliver a capacitive charging current,
nearly the total ground fault current of the system is available at the measuring point of the faulty line in the
grounded system. In the ungrounded system it is the residual wattmetric current of the Petersen coil that flows
via the measuring point. Therefore, on the faulty cables a clear "forward" decision is made whereas in other
feeders either "reverse" direction is sent back or no measurement is carried out in case ground current is too
low. Definitely the faulty line can be determined clearly.
Figure 2-87
In meshed or looped systems, the measuring points of the faulty line also receive the maximum ground fault
current (residual current). Only in this line, "forward" direction is signaled at both ends (Figure 2-88). The rest
of the direction indications in the system may also be useful for ground fault detection. However, some indica-
tions may not be given when the ground current is too low.
Figure 2-88
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
Location of ground faults in a radial network
Determination of the ground fault location basing on directional indicators in the
meshed system
2.12 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)
Functions
231