Functions
2.13 Intermittent Ground Fault Protection
The reset time, after which the summation is reset in healthy operation and the protection resumes normal
status, is configured to T-reset at address 3305.
Figure 2-94
Address 3306 Nos.det. specifies the number of pickups after which a ground fault is considered intermittent.
2.13.3
Settings
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr.
Parameter
3301
INTERM.EF
3302
Iie>
3302
Iie>
3302
Iie>
3303
T-det.ext.
3304
T-sum det.
3305
T-reset
3306
Nos.det.
248
Example of selectivity criteria of the intermittent ground fault protection
C
Setting Options
OFF
ON
1A
0.05 .. 35.00 A
5A
0.25 .. 175.00 A
1A
0.05 .. 35.00 A
5A
0.25 .. 175.00 A
0.005 .. 1.500 A
0.00 .. 10.00 sec
0.00 .. 100.00 sec
1 .. 600 sec
2 .. 10
Default Setting
OFF
Intermittent earth fault pro-
tection
1.00 A
Pick-up value of interm.
E/F stage
5.00 A
1.00 A
Pick-up value of interm.
E/F stage
5.00 A
1.000 A
Pick-up value of interm.
E/F stage
0.10 sec
Detection extension time
20.00 sec
Sum of detection times
300 sec
Reset time
3
No. of det. for start of int.
E/F prot
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008