Siemens SIPROTEC 7SJ62 Manual page 649

Multi-functional protective relay with local control
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Addr.
Parameter
7252
bef.3.Cy:50-3
7253
bef.3.Cy:50N-3
7254
bef.4.Cy:50-3
7255
bef.4.Cy:50N-3
8001
START
8101
MEASURE. SUPERV
8102
BALANCE V-LIMIT
8103
BAL. FACTOR V
8104
BALANCE I LIMIT
8105
BAL. FACTOR I
Σ I THRESHOLD
8106
Σ I FACTOR
8107
FAST Σ i MONIT
8109
8201
FCT 74TC
8202
Alarm Delay
8301
DMD Interval
8302
DMD Sync.Time
8311
MinMax cycRESET
8312
MiMa RESET TIME
8313
MiMa RESETCYCLE
8314
MinMaxRES.START
8315
MeterResolution
9011A
RTD 1 TYPE
9012A
RTD 1 LOCATION
9013
RTD 1 STAGE 1
9014
RTD 1 STAGE 1
9015
RTD 1 STAGE 2
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
Function
C
Setting Options
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=∞
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=∞
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=∞
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=∞
Fault Locator
Pickup
TRIP
Measurem.Superv
OFF
ON
Measurem.Superv
10 .. 100 V
Measurem.Superv
0.58 .. 0.90
Measurem.Superv
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
Measurem.Superv
0.10 .. 0.90
0.05 .. 2.00 A; ∞
Measurem.Superv
1A
0.25 .. 10.00 A; ∞
5A
Measurem.Superv
0.00 .. 0.95
Measurem.Superv
OFF
ON
74TC TripCirc.
ON
OFF
74TC TripCirc.
1 .. 30 sec
Demand meter
15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min.,10 Subs
5 Min., 5 Subs
Demand meter
On The Hour
15 After Hour
30 After Hour
45 After Hour
Min/Max meter
NO
YES
Min/Max meter
0 .. 1439 min
Min/Max meter
1 .. 365 Days
Min/Max meter
1 .. 365 Days
Energy
Standard
Factor 10
Factor 100
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
Default Setting
Set value T=T
before 3. Cycle: 50-3
Set value T=T
before 3. Cycle: 50N-3
Set value T=T
before 4. Cycle: 50-3
Set value T=T
before 4. Cycle: 50N-3
Pickup
Start fault locator with
ON
Measurement Supervision
50 V
Voltage Threshold for Balance
Monitoring
0.75
Balance Factor for Voltage
Monitor
0.50 A
Current Threshold for Balance
Monitoring
2.50 A
0.50
Balance Factor for Current
Monitor
0.10 A
Summated Current Monitoring
Threshold
0.50 A
0.10
Summated Current Monitoring
Factor
ON
Fast Summated Current Monitor-
ing
ON
74TC TRIP Circuit Supervision
2 sec
Delay Time for alarm
60 Min., 1 Sub
Demand Calculation Intervals
On The Hour
Demand Synchronization Time
YES
Automatic Cyclic Reset Function
0 min
MinMax Reset Timer
7 Days
MinMax Reset Cycle Period
1 Days
MinMax Start Reset Cycle in
Standard
Meter resolution
Pt 100 Ω
RTD 1: Type
Oil
RTD 1: Location
100 °C
RTD 1: Temperature Stage 1
Pickup
212 °F
RTD 1: Temperature Stage 1
Pickup
120 °C
RTD 1: Temperature Stage 2
Pickup
Appendix
A.8 Settings
Comments
649