Siemens SIPROTEC 7SJ62 Manual page 290

Multi-functional protective relay with local control
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Functions
2.17 Flexible Protection Functions
Table 2-22
Parameter in the Setting Dialog "Measurement Procedure", Mode of Operation 3-phase
Mode of Oper-
Measured
ation
Variable
Three-phase
Current,
Voltage
Current
Voltage
290
Parameter
MEAS. METHOD
Setting Options
Fundamental Harmonic
Only the fundamental harmonic is evaluated, higher harmonics
are suppressed. This is the standard measurement procedure
of the protection functions.
Important: The voltage threshold value is always parameterized
as phase-to-phase voltage independent of parameter
VOLTAGE SYSTEM.
True RMS
The "true" RMS value is determined, i.e. higher harmonics are
evaluated. This procedure is applied, for example, if an over-
load protection element must be realized on the basis of a
current measurement, as the higher harmonics contribute to
thermal heating.
Important: The voltage threshold value is always parameterized
as phase-to-phase voltage independent of parameter
VOLTAGE SYSTEM.
Positive Sequence
In order to realize certain applications, the positive sequence
System,
system or negative sequence system can be configured as
Negative Sequence
measurement procedure. Examples are:
System,
Zero Sequence System
- I2 (tripping monitoring system)
- U2 (voltage asymmetry)
Via the selection zero-sequence system, additional zero-se-
quence current or zero-sequence voltage functions can be re-
alized that operate independent of the ground variables IE and
UE, which are measured directly via transformers.
Important: The voltage threshold value is always parameterized
always parameterized according to the definition of the sym-
metrical components independent of parameter VOLTAGE
SYSTEM.
Ratio I2/I1
The ratio negative/positive sequence current is evaluated
Parameter
VOLTAGE SYSTEM
Setting Options
Phase-to-phase
If phase-to-ground voltages are connected to the device (see
Phase-to-ground
parameter address 213 VT Connect. 3ph), it can be selected
whether a three-phase operating voltage function must evalu-
ate the phase-to-ground or phase-to-phase voltages. When se-
lecting phase-to-phase, these variables are derived from the
phase-to-ground voltages. The selection is, for example, im-
portant for single-pole faults. If the faulty voltage drops to zero,
the affected phase-to-ground voltage is thus zero, and the re-
spective phase-to-phase voltages drop to the variable of a
phase-to-ground voltage.
With phase-to-phase voltage connections the parameter is
hidden.
Notes
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008