Siemens SIPROTEC 7SJ62 Manual page 221

Multi-functional protective relay with local control
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Determination of Direction
When determining the sensitive ground fault direction it is not the current value that is crucial, but the part of
the current which is perpendicular to a settable directional characteristic (axis of symmetry). As a prerequisite
for determining the direction, the displacement voltage V
part influencing the direction (active or reactive component).
The following figure illustrates an example using a complex vector diagram in which the displacement voltage
V
is the reference magnitude of the real axis. The active part 3I0
0
to the displacement voltage V
suitable for ground fault direction in grounded systems where quantity 3I
limit lines are perpendicular to axis 3I0
Figure 2-77
The directional limit lines may be rotated by a correction angle (address PHI CORRECTION) up to ± 45°. There-
fore, in grounded systems it is possible e.g. to increase sensitivity in the resistive-inductive range with a rotation
of –45°, or in case of electric machines in busbar connection in the resistive-capacitive range with a rotation of
+45° (see the following Figure). Furthermore the directional limit lines may be rotated by 90° to determine
ground faults and their direction in grounded systems.
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
and compared with setting value RELEASE DIRECT.. The example is therefore
0
.
real
Directional characteristic for cos–ϕ–measurement
2.12 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)
must be exceeded as well as a configurable current
0
of current 3I
is calculated with reference
real
0
· cos ϕ is relevant. The directional
0
Functions
221

Advertisement

Table of Contents
loading

Table of Contents