Ground Fault Protection 64, 67N(S), 50N(S), 51N(S) - Siemens SIPROTEC 7SJ62 Manual

Multi-functional protective relay with local control
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Technical Data

4.16 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)

4.16
Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)
Displacement Voltage Pickup for All Types of Ground Faults
Displacement voltage, measured
Displacement voltage, calculated
Pickup delay T-DELAY Pickup
Additional tripping delay 64-1 DELAY
Operating time
Dropout value
Measurement tolerance
V
(measured)
0
V
(calculated)
0
Operating time tolerances
Phase Detection for Ground Faults on an Ungrounded System
Measuring Principle
V
(Ground Fault Phase)
PHASE MIN
V
(Healthy Phase)
PHASE MAX
Measurement Tolerance acc. to VDE 0435, Part 303 3 % of setting value or 1 V
Ground Fault Pickup for All Types of Ground Faults (Definite Time Characteristic)
Pickup current 50Ns-2 PICKUP
for sensitive transformer
for normal 1-A transformer
for normal 5-A transformer
Time Delay 50Ns-2 DELAY
Pickup current 50Ns-1 PICKUP
for sensitive transformer
for normal 1-A transformer
for normal 5-A transformer
Time Delay 50Ns-1 DELAY
Dropout Time Delay 50Ns T DROP-OUT
Operating Time
Dropout Ratio
Measurement Tolerance
Operating Time Tolerance
512
V
1.8 V to 170.0 V or
0
∞(disabled) (7SJ62)
V0 0.4 V to 200.0 V or
∞(disabled) (7SJ64)
VV
> 10.0 V to 225.0 V
GND
0.04 s to 320.00 s or ∞
0.10 s to 40000.00 s or ∞ (disabled)
approx. 50 ms
0.95 or (pickup value – 0.6 V)
3 % of setting value or 0.3 V
3 % of setting value or 3 V
1 % of setting value or 10 ms
Voltage measurement (phase-ground)
10 V to 100 V
10 V to 100 V
0.001 A to 1.500 A
0.05 A to 35.00 A
0.25 A to 175.00 A
0.00 s to 320.00 s or ∞ (disabled)
0.001 A to 1.500 A
0.05 A to 35.00 A
0.25 A to 175.00 A
0.00 s to 320.00 s or ∞ (disabled)
0.00 s to 60.00 s
≤ 50 ms (non-directional)
≤ 50 ms (directional)
Approx. 0.95 for 50Ns >50 mA
2 % of setting value or 1 mA
1 % of setting value or 10 ms
C53000-G1140-C207-2, Release date 01.2008
Increments 0.1V
Increments 0.1V
Increments 0.01 s
Increments 0.01 s
Increments 1V
Increments 1V
Increments 0.001 A
Increments 0.01 A
Increments 0.05 A
Increments 0.01 s
Increments 0.001 A
Increments 0.01 A
Increments 0.05 A
Increments 0.01 s
Increments 0.01 s