Siemens SIPROTEC 7SJ62 Manual page 645

Multi-functional protective relay with local control
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Addr.
Parameter
6446
T SYNC-DELAY
6450
dV SYNCHK V2>V1
6451
dV SYNCHK V2<V1
6452
df SYNCHK f2>f1
6453
df SYNCHK f2<f1
dα SYNCHK α2>α1
6454
dα SYNCHK α2<α1
6455
7001
FCT 50BF
7004
Chk BRK CONTACT
7005
TRIP-Timer
7006
50BF PICKUP
7007
50BF PICKUP IE>
7101
FCT 79
7103
BLOCK MC Dur.
7105
TIME RESTRAINT
7108
SAFETY 79 ready
7113
CHECK CB?
7114
T-Start MONITOR
7115
CB TIME OUT
7116
Max. DEAD EXT.
7117
T-ACTION
7118
T DEAD DELAY
7127
DEADTIME 1: PH
7128
DEADTIME 1: G
7129
DEADTIME 2: PH
7130
DEADTIME 2: G
7131
DEADTIME 3: PH
7132
DEADTIME 3: G
7133
DEADTIME 4: PH
7134
DEADTIME 4: G
7135
# OF RECL. GND
7136
# OF RECL. PH
7137
Cmd.via control
7138
Internal SYNC
7139
External SYNC
7140
ZONE SEQ.COORD.
7150
50-1
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
Function
C
Setting Options
SYNC function 4
0.00 .. 60.00 sec
SYNC function 4
0.5 .. 50.0 V
SYNC function 4
0.5 .. 50.0 V
SYNC function 4
0.01 .. 2.00 Hz
SYNC function 4
0.01 .. 2.00 Hz
SYNC function 4
2 .. 80 °
SYNC function 4
2 .. 80 °
50BF BkrFailure
OFF
ON
50BF BkrFailure
OFF
ON
0.06 .. 60.00 sec; ∞
50BF BkrFailure
50BF BkrFailure
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
50BF BkrFailure
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
79M Auto Recl.
OFF
ON
79M Auto Recl.
0.50 .. 320.00 sec; 0
79M Auto Recl.
0.50 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
No check
Chk each cycle
0.01 .. 320.00 sec; ∞
79M Auto Recl.
79M Auto Recl.
0.10 .. 320.00 sec
0.50 .. 1800.00 sec; ∞
79M Auto Recl.
0.01 .. 320.00 sec; ∞
79M Auto Recl.
0.0 .. 1800.0 sec; ∞
79M Auto Recl.
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0 .. 9
79M Auto Recl.
0 .. 9
79M Auto Recl.
(Setting options depend
on configuration)
79M Auto Recl.
(Setting options depend
on configuration)
79M Auto Recl.
YES
NO
79M Auto Recl.
OFF
ON
79M Auto Recl.
No influence
Starts 79
Stops 79
Default Setting
0.00 sec
Release delay at synchronous
conditions
5.0 V
Maximum voltage difference
V2>V1
5.0 V
Maximum voltage difference
V2<V1
0.10 Hz
Maximum frequency difference
f2>f1
0.10 Hz
Maximum frequency difference
f2<f1
10 °
Maximum angle difference
alpha2>alpha1
10 °
Maximum angle difference
alpha2<alpha1
OFF
50BF Breaker Failure Protection
OFF
Check Breaker contacts
0.25 sec
TRIP-Timer
0.10 A
50BF Pickup current threshold
0.50 A
0.10 A
50BF Pickup earth current
threshold
0.50 A
OFF
79 Auto-Reclose Function
1.00 sec
AR blocking duration after
manual close
3.00 sec
79 Auto Reclosing reset time
0.50 sec
Safety Time until 79 is ready
No check
Check circuit breaker before AR?
0.50 sec
AR start-signal monitoring time
3.00 sec
Circuit Breaker (CB) Supervision
Time
100.00 sec
Maximum dead time extension
∞ sec
Action time
1.0 sec
Maximum Time Delay of Dead-
Time Start
0.50 sec
Dead Time 1: Phase Fault
0.50 sec
Dead Time 1: Ground Fault
0.50 sec
Dead Time 2: Phase Fault
0.50 sec
Dead Time 2: Ground Fault
0.50 sec
Dead Time 3: Phase Fault
0.50 sec
Dead Time 3: Ground Fault
0.50 sec
Dead Time 4: Phase Fault
0.50 sec
Dead Time 4: Ground Fault
1
Number of Reclosing Cycles
Ground
1
Number of Reclosing Cycles
Phase
None
Close command via control
device
None
Internal 25 synchronisation
NO
External 25 synchronisation
OFF
ZSC - Zone sequence coordina-
tion
No influence
50-1
Appendix
A.8 Settings
Comments
645