Siemens SIPROTEC 7SJ62 Manual page 638

Multi-functional protective relay with local control
Hide thumbs Also See for SIPROTEC 7SJ62:
Table of Contents

Advertisement

Appendix
A.8 Settings
Addr.
Parameter
4002
46-1 PICKUP
4003
46-1 DELAY
4004
46-2 PICKUP
4005
46-2 DELAY
4006
46 IEC CURVE
4007
46 ANSI CURVE
4008
46-TOC PICKUP
4009
46-TOC TIMEDIAL
4010
46-TOC TIMEDIAL
4011
46-TOC RESET
4012A
46 T DROP-OUT
4101
FCT 48/66
4102
STARTUP CURRENT
4103
STARTUP TIME
4104
LOCK ROTOR TIME
4105
STARTUP T WARM
4106
TEMP.COLD MOTOR
4201
FCT 49
4202
49 K-FACTOR
4203
TIME CONSTANT
49 Θ ALARM
4204
4205
I ALARM
4207A
Kτ-FACTOR
4208A
T EMERGENCY
4209
49 TEMP. RISE I
4210
49 TEMP. RISE I
4301
FCT 66
4302
IStart/IMOTnom
4303
T START MAX
4304
T Equal
4305
I MOTOR NOMINAL
4306
MAX.WARM STARTS
4307
#COLD-#WARM
4308
Kτ at STOP
4309
Kτ at RUNNING
4310
T MIN. INHIBIT
638
Function
C
Setting Options
46 Negative Seq
1A
0.10 .. 3.00 A
5A
0.50 .. 15.00 A
0.00 .. 60.00 sec; ∞
46 Negative Seq
46 Negative Seq
1A
0.10 .. 3.00 A
5A
0.50 .. 15.00 A
0.00 .. 60.00 sec; ∞
46 Negative Seq
46 Negative Seq
Normal Inverse
Very Inverse
Extremely Inv.
46 Negative Seq
Extremely Inv.
Inverse
Moderately Inv.
Very Inverse
46 Negative Seq
1A
0.10 .. 2.00 A
5A
0.50 .. 10.00 A
0.50 .. 15.00 ; ∞
46 Negative Seq
0.05 .. 3.20 sec; ∞
46 Negative Seq
46 Negative Seq
Instantaneous
Disk Emulation
46 Negative Seq
0.00 .. 60.00 sec
48/66 Motorprot
OFF
ON
48/66 Motorprot
1A
0.50 .. 16.00 A
5A
2.50 .. 80.00 A
48/66 Motorprot
1.0 .. 180.0 sec
0.5 .. 180.0 sec; ∞
48/66 Motorprot
0.5 .. 180.0 sec; ∞
48/66 Motorprot
0 .. 80 %; ∞
48/66 Motorprot
49 Th.Overload
OFF
ON
Alarm Only
49 Th.Overload
0.10 .. 4.00
49 Th.Overload
1.0 .. 999.9 min
49 Th.Overload
50 .. 100 %
49 Th.Overload
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
49 Th.Overload
1.0 .. 10.0
49 Th.Overload
10 .. 15000 sec
49 Th.Overload
40 .. 200 °C
49 Th.Overload
104 .. 392 °F
48/66 Motorprot
OFF
ON
48/66 Motorprot
1.10 .. 10.00
48/66 Motorprot
1 .. 320 sec
48/66 Motorprot
0.0 .. 320.0 min
48/66 Motorprot
1A
0.20 .. 1.20 A
5A
1.00 .. 6.00 A
48/66 Motorprot
1 .. 4
48/66 Motorprot
1 .. 2
48/66 Motorprot
0.2 .. 100.0
48/66 Motorprot
0.2 .. 100.0
48/66 Motorprot
0.2 .. 120.0 min
Default Setting
0.10 A
46-1 Pickup
0.50 A
1.50 sec
46-1 Time Delay
0.50 A
46-2 Pickup
2.50 A
1.50 sec
46-2 Time Delay
Extremely Inv.
46 IEC Curve
Extremely Inv.
46 ANSI Curve
0.90 A
46-TOC Pickup
4.50 A
5.00
46-TOC Time Dial
0.50 sec
46-TOC Time Dial
Instantaneous
46-TOC Drop Out
0.00 sec
46 Drop-Out Time Delay
OFF
48 / 66 Motor (Startup Moni-
tor/Counter)
5.00 A
Startup Current
25.00 A
10.0 sec
Startup Time
2.0 sec
Permissible Locked Rotor Time
10.0 sec
Startup Time for warm motor
25 %
Temperature limit for cold motor
OFF
49 Thermal overload protection
1.10
49 K-Factor
100.0 min
Time Constant
90 %
49 Thermal Alarm Stage
1.00 A
Current Overload Alarm Setpoint
5.00 A
1.0
Kt-FACTOR when motor stops
100 sec
Emergency time
100 °C
49 Temperature rise at rated sec.
curr.
212 °F
49 Temperature rise at rated sec.
curr.
OFF
66 Startup Counter for Motors
4.90
I Start / I Motor nominal
10 sec
Maximum Permissible Starting
Time
1.0 min
Temperature Equalizaton Time
1.00 A
Rated Motor Current
5.00 A
2
Maximum Number of Warm
Starts
1
Number of Cold Starts - Warm
Starts
5.0
Extension of Time Constant at
Stop
2.0
Extension of Time Constant at
Running
6.0 min
Minimum Restart Inhibit Time
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008