4.3.7.3

Motor stop time monitoring

Motor stop time monitoring - use
System parts for important processes often have dual drives (A and B drives). Ensure that
these are always operated alternately. This prevents long motor stop times and reduces the
risk of non-availability.
The motor stop time monitoring function can be used, for example, to generate an interrupt,
thus initiating connection of the motor.
Level
The length of the permissible motor stop time is stipulated here; if exceeded, the monitoring
function responds.
Level
Active status
Unless deactivated, this function is always active, independent of whether the motor is
running or not (operating state "ON").
Response
You can define the response to overshoot of the permissible stop time here:
See also "Tables of responses of SIMOCODE pro" in Important information (Page 7) and
Table "Response of operation monitoring" in Description of functions of operation monitoring
(Page 150).
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
4.3 Monitoring functions
0 to 65535 hours (default: 0 h)