Siemens SIMOCODE pro Operating Manual page 169

Industrial controls, motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Schematic
The following schematic shows the "DM Outputs" function blocks:
Figure 4-49
Application examples
● Activation of the motor contactor in the motor feeder:
You can, for example, define which relay output is to be used for activating the main
contactor in the motor feeder. To do this, connect the desired relay output to the
respective "QE" contactor control of the control function.
● Activation of lamps for displaying operating states:
You can define, for example, which relay outputs are to be used for controlling the
lamps/LEDs that display the operating states of the motor (Fault, ON, OFF, FAST, SLOW
...). To do this, connect the desired relay output to the respective "QL..." lamp control of
the control function.
● Transfer of any other information, status information, warnings, faults, etc. to the relay
outputs.
In many cases, the outputs of the digital module will be connected to the QE outputs. By
referring to Table Active control stations, contactor controls, lamp controls and status
information for the control functions (Page 119), you can determine which QE outputs are
required for which control functions.
Settings
Table 4- 53
"DM1 / DM2 Outputs"
Outputs 1 to 2
Defaults depend on the selected application (template): See Chapter Application selection,
settings and definitions of control functions (Page 66).
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
Schematic of the "DM1 Outputs" / "DM2 Outputs" function blocks
"DM1 / DM2 Outputs" settings
Control of the "DM1 Outputs" and "DM2 Outputs" function blocks via any
signal (any socket, e.g. device inputs, PROFIBUS DP control bits, etc.
usually from the QE contactor controls.)
Description
Parameters
4.4 Outputs
169