Siemens SIMOCODE pro Operating Manual page 195

Industrial controls, motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Application examples
Typical applications are:
● Fill-level monitoring for implementing dry running protection for pumps
● Monitoring of pollution in a filter using a differential pressure transducer.
Settings
Table 4- 65
Analog module
Input signal
Response to open circuit
Active inputs
Notes
Note
The value of the analog module inputs is in S7 format.
Note
The inputs of the analog module are passive inputs, i.e. to configure an analog input circuit,
each input will require an additional, isolated external current source connected in series. If
the output of the analog module is not being used by another application, it can also be used
as a current source for an analog module input circuit. The "Start value of value range" and
the "End value of value range" of the analog module output have to be set to 65535 for this.
Thus, the maximum possible current will always be available via the analog module output.
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
Analog module input settings
Description
0 to 20mA (default), 4 to 20 mA
Signal, warn (default), tripping
1 input (default), 2 inputs
Parameters
4.5 Inputs
195