Siemens SIMOCODE pro Operating Manual page 85

Industrial controls, motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Settings
You will find detailed explanations of the settings in Chapter Application selection, settings
and definitions of control functions (Page 66).
Table 4- 14
Star-delta starter settings
Star-delta starter
OFF
ОN >
FB ON
Non-maintained command
mode
Separate fail-safe function from
control function
Load type
Feedback time
Execution time
Change-over pause
Max. star time
Current measuring module
installed
1)
Note
1) If a current / voltage measuring module is in use, the transformer must be connected in
the supply cable!
It is also necessary to select "Line-to-line voltage" under "Device configuration → Voltage
display".
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
Description
Control command OFF
(Connection with any socket, usually with "Enabled control command OFF" socket)
Control command ON
(Connection with any socket, usually with "Enabled control command ON >" socket)
Auxiliary control input "Feedback ON" (connection with any socket, usually with "Status -
current flowing" socket)
Deactivated (default setting)
Activated
Deactivated (default setting): A safety-related tripping by the DM-F modules affects
the SIMOCODE pro control function, avoiding additional follow-on fault messages.
This setting is selected for applications where safety-related tripping directly affects
the motor controlled by SIMOCODE pro.
Activated: A safety-related disconnection by the DM-F modules does not affect the
SIMOCODE pro control function. This setting is selected for applications where
safety-related tripping does not affect the motor controlled by SIMOCODE pro.
You can select from the following:
Motor (default)
Resistive load (see Chapter Application selection, settings and definitions of control
functions (Page 66))
Range 0 to 25.5 s (default: 0.5 s)
Range 0 to 6553.5 s (default: 1 s)
Range 0 to 655.3 s (10 ms steps) (default: 0.00 s)
Time-dependent switching from star to delta.
Range 0 to 255 s (default: 20 s)
The current setting and the switching levels for star-to-delta switching depend on the
installation location of the current measuring module:
In delta circuit: Current setting I
In supply cable: Current setting I
is reduced to I
x 1/√3 (default)
s
n
= I
(rated current of the motor)
s
n
Parameters
4.2 Motor control
85