Parameters
4.3 Monitoring functions
Active status of trip and warning levels
The trip level / warning level is active only when the motor is running, the startup procedure
has been completed and there is no test position feedback (TPF) (run+).
Response to trip level
Here you can define how SIMOCODE pro will respond if the set trip level is undershot:
See also "Tables of responses of SIMOCODE pro" in Chapter Important information
(Page 7).
Table 4- 40
Response
Deactivated
signal
warn
tripping
Delay
Response to warning level
Here you can define how SIMOCODE pro will respond if the set warning level is undershot.
See also "Tables of responses of SIMOCODE pro" in Chapter Important information
(Page 7).
Table 4- 41
Response
Deactivated
signal
warn
tripping
Delay
144
"Trip level" response for cos phi monitoring
"Warning level" response for cos phi monitoring
Trip level
X (d)
X
—
X
0 to 25.5 s (default: 0.5 s)
Warning level
X (d)
X
X
—
0 to 25.5 s (default: 0.5 s)
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001