Schematic
The following schematic shows the "Timers" logic modules:
Figure 4-96
Note
The output is always 0 if a reset is pending.
Note
The response of the plugs of all timers (input, reset) has been completely changed to level-
active for the SIMOCODE pro C basic unit from version *E05* and higher and the
SIMOCODE pro V PB basic unit from version *E03* and higher. Use of an unchanged
parameter file utilizing integrated timers may thus result in a different response if such basic
units are used. For example, if "Fixed level - '1'" is set at the timer input, the timer function is
automatically restarted after the timer reset occurs. However, in timers with the
parameterized type = "Fleeting closing" there is no change in the response.
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
"Timer" logic modules
Parameters
4.8 Logic modules
243