External Ground-Fault Monitoring With A 3Uf7510 Ground-Fault Module And 3Ul23 Residual Current Transformer - Siemens SIMOCODE pro Operating Manual

Industrial controls, motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Parameters
4.3 Monitoring functions
4.3.1.6
External ground-fault monitoring with a 3UF7510 ground-fault module and 3UL23
residual current transformer
Settings
You can parameterize two different response levels (trip level, warning level) for monitoring
the ground-fault current.
If the ground-fault current exceeds the response level, the current limit monitoring will
respond.
See also "Tables of responses of SIMOCODE pro" in Chapter Important information
(Page 7).
Figure 4-32
"Ground-fault Monitoring" function block
Trip level, warning level
You can parameterize two different response levels (trip level, warning level) for monitoring
the ground-fault current.
If the ground-fault current exceeds the response level, the current limit monitoring will
respond.
Trip level:
Warning level:
132
30 mA to 40 A in steps of 10 mA (default: 1000 mA)
20 mA to 40 A in steps of 10 mA (default: 500 mA)
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001