Parameters
4.3 Monitoring functions
4.3.2.3
I< (lower limit)
Trip level / warning level
When monitoring current limits I< (lower limit), two different response levels (trip level /
warning level) can be parameterized and monitored:
● I< (lower limit) trip level
● I< (lower limit) warning level
If the current of the phases (I
responds.
Trip level
Warning level
Active status of trip and warning levels
The trip level / warning level is active only when the motor is running, the startup procedure
has been completed and there is no test position feedback (TPF) (run+).
Response to trip level
Here you can define how SIMOCODE pro will respond if the trip level is undershot:
See also "Tables of responses of SIMOCODE pro" in Chapter Important information
(Page 7).
Table 4- 36
Response
Deactivated
signal
warn
tripping
Delay
138
) drops below the response level, the current limit monitor
max
0 to 1020 % of l
0 to 1020 % of l
"Trip level" response for monitoring current limits I <
in steps of 4% (default: 0)
s
in steps of 4% (default: 0)
s
Trip level
X (d)
X
X
0 to 25.5 s (default: 0.5 s)
SIMOCODE pro - Parameterize