Table 4- 62
Inputs
Debounce time
Note
The debounce times of the digital module inputs can only be set and/or are only relevant
when "monostable" or "bistable" is set for digital module 1.
The debounce time cannot be set if digital module 1 is a DM-F PROFIsafe.
If digital module 1 is a DM-F Local, the debounce times can be set using the DIP switches on
the front of the DM-F Local.
Non-safety functions (fail-safe digital modules)
● If digital module1 is a DM-F Local, it is a digital module with non-safety inputs, relay
outputs and diagnostics in a SIMOCODE pro system.
● If digital module 1 is a DM-F PROFIsafe, it is a digital module with non-safety inputs, relay
outputs and diagnostics in a SIMOCODE pro system.
Detailed information on fail-safe digital modules: See "Description of system
components → Fail-safe digital modules" in the SIMOCODE pro system manual.
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
"DM1 / DM2 Inputs" settings
You can set a debounce time for the inputs, if required.
Range: 6, 16, 26, 36 ms (default: 16 ms). These values apply to digital modules
with a 24 V DC input supply.
The values are approximately 40 ms higher for digital modules with input
supplies of 110 to 240 VAC/DC.
Description
Parameters
4.5 Inputs
191