Settings
You will find detailed explanations of the settings in Chapter Application selection, settings
and definitions of control functions (Page 66).
Table 4- 13
Circuit breaker settings
Circuit breaker
OFF
ОN >
FB ON
Non-maintained command mode
Separate fail-safe function from
control function
Load type
Feedback time
Execution time
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
Description
Control command OFF
(Connection with any socket, usually with "Enabled control command OFF" socket)
Control command ON
(Connection with any socket, usually with "Enabled control command ON >" socket)
Auxiliary control input "Feedback ON" (connection always with socket, (input), that
the auxiliary switch of the circuit breaker is connected to).
Deactivated (default setting)
•
Activated
•
Deactivated (default setting): A safety-related tripping by the DM-F modules also
•
affects the SIMOCODE pro control function, avoiding additional follow-on fault
messages. This setting is selected for applications where safety-related tripping
directly affects the motor controlled by SIMOCODE pro.
Activated: A safety-related tripping by the DM-F modules does not affect the
•
SIMOCODE pro control function. This setting is selected for applications where
safety-related tripping does not affect the motor controlled by SIMOCODE pro.
You can choose between:
Motor (default)
•
Resistive load (see Chapter Application selection, settings and definitions of
•
control functions (Page 66))
A repeated ON pulse is only output by the QE1 contactor control once the set
feedback time has elapsed. The feedback time should therefore be set higher than
the motor off time of the motorized operating mechanism of the circuit breaker.
Range 0 to 25.5 s (default: 0.5 s)
Range 0 to 6553.5 s (default: 1.0 s)
Parameters
4.2 Motor control