Parameters
4.3 Monitoring functions
Marking
The marking is saved in the device and assigned and displayed in the Faults / Warnings
online dialog. Optional marking for identifying the message, e.g. "0/4 to 20 >"; range:
maximum 10 characters.
Note
Changing the marking of Ethernet and PROFINET connections
Each change to the marking requires that the communication interface be restarted when the
web server is active. A new start interrupts all Ethernet and PROFINET links and
reestablishes them afterward.
Hysteresis for 0/4 to 20 mA
Here you can set the fluctuation range for the analog signal:
Hysteresis for the analog signal
Note
Monitoring of a second process variable via input 2 of the analog module can be done, for
example, by free limit monitors.
4.3.7

Operation monitoring

4.3.7.1

Description of functions of operation monitoring

Motor operation monitoring - use
SIMOCODE pro can monitor the operating hours and stop times of a motor and restrict the
number of startups in a defined time frame to avoid plant downtimes due to failed motors
caused by running or being stopped for too long.
If an adjustable limit value is exceeded, a signal or warning can be generated that indicates
maintenance or replacement of the motor in question is required. After the motor has been
replaced, the operating hours and stop times can be reset, for example.
To avoid excessive thermal loads and premature wear of the motor, it is possible to limit the
number of motor startups for a specifiable period. The number of still possible starts is
available in the SIMOCODE pro for further processing.
150
0 to 15 % in steps of 1 % (default: 5 %)