As a result,
● The "Start value of value range" to be selected is: 0
● The "End value of value range" to be selected is: 400.
Figure 4-52
When the parameterized "Output signal" = 0 to 20 mA:
● 0 % motor current: 0 mA at the analog module output
● 400 % motor current: 20 mA at the analog module output.
When the parameterized "Output signal" = 4 to 20 mA:
● 0 % motor current: 4 mA at the analog module output
● 400 % motor current: 20 mA at the analog module output.
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
Application example: Motor current output - output values to function block AM output
Parameters
4.4 Outputs