Voltage Monitoring - Siemens SIMOCODE pro Operating Manual

Industrial controls, motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Parameters
4.3 Monitoring functions
4.3.3

Voltage monitoring

Description
SIMOCODE pro supports two-phase undervoltage monitoring of either a three-phase
network or a single-phase network for freely selectable limits. The response of
SIMOCODE pro on reaching a prewarning level or trip level can be freely parameterized and
delayed.
Voltage measurement is performed using current / voltage measuring modules. This is
based on the minimum voltage of all voltages U
Note
Please note that only phase voltages are available with SIMOCODE pro V PB basic units up
to version *E06*. If required, the line-to-line voltage can be calculated from the phase voltage
using the logic module "Calculator 1/2" as follows: Line-to-line voltage = phase
voltage * 1.73.
From version *E07* onward, either phase voltage or line-to-line voltage can be used as the
basis for monitoring.
Figure 4-34
Furthermore, even when the motor is switched off, SIMOCODE pro can determine and
signal the further availability of the feeder by measuring the voltage directly at the circuit
breaker or at the fuses in the main circuit.
140
"Voltage Monitoring" function block
.
min
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001