Parameters
4.8 Logic modules
Timer settings
Table 4- 89
Timer settings
Timers 1 to 6
Description
Input
Activation by any signal (any sockets, e.g. device inputs, control bits from the communication bus, etc.)
Reset
Resetting the actual value to 0.
Activation by any signal (any sockets, e.g. device inputs, control bits from the communication bus, etc.)
Type
Different output responses
Range: With closing delay (default), closing delay with memory, with OFF delay, with fleeting closing
Value
Time during which the timer provides an output signal when activated, depending on the output response
(type).
Range: 0 to 6553.5, unit 100 ms (default: 0)
246
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001