Siemens SIMOCODE pro Operating Manual page 73

Industrial controls, motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Settings
You will find detailed explanations of the settings in Chapter Application selection, settings
and definitions of control functions (Page 66).
Table 4- 10
Overload relay settings
Overload relay
Description
FB ON
"Feedback ON" auxiliary control input
Connection with any socket, usually with "Status - current flowing" socket
Load type
You can choose between:
Separate fail-safe
function from control
function
Note
In the case of overload, the QE3 output is set (=1) and is only reset after an overload trip
(=0).
This output closes when the overload function is parameterized.
Note
Monitoring the number of starts is not possible for this control function.
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
Motor (default)
Resistive load (see Chapter Application selection, settings and definitions of control functions
(Page 66))
Deactivated (default setting): A safety-related tripping by the DM-F modules affects the
SIMOCODE pro control function, avoiding additional follow-on fault messages. This setting is
selected for applications where safety-related tripping directly affects the motor controlled by
SIMOCODE pro.
Activated: A safety-related disconnection by the DM-F modules does not affect the
SIMOCODE pro control function. This setting is selected for applications where safety-related
tripping does not affect the motor controlled by SIMOCODE pro.
Parameters
4.2 Motor control
73