Parameters
4.3 Monitoring functions
Response
See also "Tables of responses of SIMOCODE pro" in Chapter Important information
(Page 7).
● Overtemperature: Here you can select how SIMOCODE pro should respond when the
temperature has overshot the warning level / trip level.
Table 4- 48
Response
disabled
signaling
warn
tripping
Note
With motors for EEx e applications, the response must be set to "tripping"!
Note
The sensor type, the number of measuring circuits in use and the response to a sensor fault
must be set in the Temperature module inputs (TM1 / 2 inputs) function block if temperature
monitoring is used.
Note
To monitor several sensor measuring circuits individually and independently, a suitable
number of free limit monitors can be connected to the temperature module inputs (TM1 / 2
inputs) function block and differing limits set for the individual temperature sensors, instead
of the temperature monitoring function block.
158
"Overtemperature" response
Warning level T >
X
X
X (d)
Trip level T >
X
X (d)
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001