When the module-specific backup parameter is not used

Medium speed
When the module-specific backup parameter is not used, back up and restore offset/gain values by one of the following
methods.
• Saving and restoring with dedicated instructions
• Saving and restoring by reading from and writing to the buffer memory
With the methods above, offset/gain values can be restored to a new module, or the offset/gain values set in one module can
be applied to the other modules in the same system.
• To restore offset/gain values onto a new replaced module:
1 FUNCTIONS
142
1.21 Backing up, Saving, and Restoring Offset/Gain Values
Low speed
1.
Save the offset/gain values.
2.
Replace the A/D converter module.
3.
Restore the offset/gain values.