Setting procedure
1.
Select a detection method in "Input signal error detection setting".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Application setting]  [Input
signal error detection function]
2.
Set values for "Input signal error detection lower limit setting value" and "Input signal error detection upper limit setting
value".
Item
Input signal error detection lower limit setting value
Input signal error detection upper limit setting value
3.
Set "Input signal error detection auto clear enable/disable setting" to "Enable" or "Disable".
Setting range
0.0 to 25.0 (%)
1.12 Input Signal Error Detection Function