Mitsubishi Electric MELSEC iQ-R User Manual page 225

High speed analog-digital converter module
Hide thumbs Also See for MELSEC iQ-R:
Table of Contents

Advertisement

CH1 Rate alarm warning detection cycle setting
Medium speed
Low speed
Set the cycle to check the change rate of digital output values.
The value of the cycle to detect a rate alarm warning is the product of the value in 'CH1 Rate alarm warning detection cycle
setting' (Un\G522) and the conversion cycle.
For details on the warning output function (rate alarm), refer to the following.
Page 55 Rate alarm
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Rate alarm warning detection cycle setting
■Setting range
The setting range is from 1 to 32000 (times).
In the channel where a value out of the range is set, a rate alarm warning detection cycle setting range error (error code:
1B9H) occurs.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is 0 for all channels.
CH1 Rate alarm upper limit value
Medium speed
Low speed
For rate alarm, the digital output value is checked at every warning detection cycle and the change rate is calculated from the
check result. Use this area to set an upper limit value of the change rate of digital output values for each channel.
For details on the warning output function (rate alarm), refer to the following.
Page 55 Rate alarm
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Rate alarm upper limit value
■Setting range
The setting range is from -32768 to 32767 (-3276.8 to 3276.7%). (Set it in increments of 0.1%.)
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is 0 for all channels.
CH1
CH2
522
722
CH1
CH2
524
724
CH3
CH4
922
1122
CH3
CH4
924
1124
APPX
Appendix 3 Buffer Memory Areas
A
223