Error code
Error name
1862H
Model mismatch error at the
execution of OGSTOR
190H
Range setting range error
191H
Averaging process
specification setting range
error
192H
Time average setting range
error
193H
Count average setting range
error
194H
Moving average setting
range error
195H
Primary delay filter constant
setting range error
196H
Low pass filter setting range
error
3 TROUBLESHOOTING
160
3.4 List of Error Codes
Description and cause
The G(P).OGSTOR instruction has been executed
on a module different from the one on which the
G(P).OGLOAD instruction was executed.
The G(P).OGSTOR instruction has been executed
ahead of the G(P).OGLOAD instruction.
A value out of the range is set in CH Range
setting.
A value out of the range is set in CH Averaging
process specification.
When the time average is set in CH Averaging
process specification, a value other than 1 to 5000 is
set in CH Time average/Count average/Moving
average/Primary delay filter constant setting.
When the count average is set in CH Averaging
process specification, a value other than 4 to 62500
is set in CH Time average/Count average/Moving
average/Primary delay filter constant setting.
When the moving average is set in CH Averaging
process specification, a value other than 2 to 1000 is
set in CH Time average/Count average/Moving
average/Primary delay filter constant setting.
When the primary delay filter is set in CH
Averaging process specification, a value other than
1 to 500 is set in CH Time average/Count average/
Moving average/Primary delay filter constant setting.
A value out of the range is set in CH LPF Pass
band edge frequency or CH Attenuation band
width.
Action
Execute the G(P).OGLOAD and G(P).OGSTOR
instructions on the same module. As the other way,
execute the G(P).OGLOAD instruction on the
module whose data is to be restored, and then
execute the G(P).OGSTOR instruction on the
module to which the data is to be restored.
Set CH Range setting to the following values:
• 4 to 20mA (0H) to 0 to 10V (5H)
• 4 to 20mA (extended mode) (AH)
• 1 to 5V (extended mode) (BH)
• User range setting (FH)
■Normal mode (medium speed: 10s/CH), normal
mode (low speed: 20s/CH)
Set CH Averaging process specification to
Sampling processing (0) to Band pass filter (7).
■Normal mode (high speed: 1s/CH), simultaneous
conversion mode, inter-module synchronization
mode
Set CH Averaging process specification to
Sampling processing (0) or Moving average (3).
Set CH Time average/Count average/Moving
average/Primary delay filter constant setting to 1 to
5000.
Set CH Time average/Count average/Moving
average/Primary delay filter constant setting to 4 to
62500.
Set CH Time average/Count average/Moving
average/Primary delay filter constant setting to 2 to
1000.
Set CH Time average/Count average/Moving
average/Primary delay filter constant setting to 1 to
500.
Set CH LPF Pass band edge frequency and CH
Attenuation band width to the following values:
■When the conversion cycle is 10s
• Pass band edge frequency + Attenuation band
width 48000
• Attenuation band width 1300
• Pass band edge frequency 0
■When the conversion cycle is 20s
• Pass band edge frequency + Attenuation band
width 24000
• Attenuation band width 650
• Pass band edge frequency 0
■When the conversion cycle is 30s
• Pass band edge frequency + Attenuation band
width 16000
• Attenuation band width 440
• Pass band edge frequency 0
■When the conversion cycle is 40s
• Pass band edge frequency + Attenuation band
width 12000
• Attenuation band width 330
• Pass band edge frequency 0
■When the conversion cycle is 60s
• Pass band edge frequency + Attenuation band
width 8000
• Attenuation band width 220
• Pass band edge frequency 0
■When the conversion cycle is 80s
• Pass band edge frequency + Attenuation band
width 6000
• Attenuation band width 170
• Pass band edge frequency 0