Range Switching Function - Mitsubishi Electric MELSEC iQ-R User Manual

High speed analog-digital converter module
Hide thumbs Also See for MELSEC iQ-R:
Table of Contents

Advertisement

1.3

Range Switching Function

Common
This function switches the input range of an analog input for each channel.
Switching the range makes it possible to change the I/O conversion characteristics.
Setting procedure
Set the input range to be used in the "Input range setting".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Basic setting]  [Range
switching function]
Input range setting
4 to 20mA
0 to 20mA
1 to 5V
0 to 5V
-10 to 10V
0 to 10V
4 to 20mA (Extension)
1 to 5V (Extension)
User range
After the data is written, the range is switched when the programmable controller power supply is turned off and on or when
the CPU module is reset.
With the following buffer memory areas, the range switching and range setting can be monitored.
'CH1 Range setting' (Un\G598)
'CH1 Range setting monitor' (Un\G430)
For details on the buffer memory addresses, refer to the following.
Page 236 CH1 Range setting
Page 203 CH1 Range setting monitor
Precautions
The input range cannot be switched for the channel where A/D conversion disable is set. To switch the input range, set "A/D
conversion enable/disable setting" to "A/D conversion enable".
Digital output value
0 to 32000
-32000 to 32000
0 to 32000
-8000 to 32000
-32000 to 32000