Mitsubishi Electric MELSEC iQ-R User Manual page 112

High speed analog-digital converter module
Hide thumbs Also See for MELSEC iQ-R:
Table of Contents

Advertisement

■Stopping continuous logging
A continuous logging stop request is sent at every inter-module synchronization cycle in the same way as when continuous
logging is started. Thus, logged data is stored in the buffer memory in the next inter-module synchronization cycle after the
continuous logging stop request is accepted. After the data has been stored, 'Continuous logging status monitor' (Un\G61) is
set to Continuous logging start request waiting (1).
'CH1 Synchronization digital
output value' (Un\G9500)
'Continuous logging start/stop
request' (Un\G100)
'Continuous logging status
monitor' (Un\G61)
Logging timing
Continuous logging data storage
'CH1 Number of logging data'
(Un\G440, Un\G441)
'CH1 Continuous logging data
A side storage flag' (Un\G474)
'CH1 Continuous logging data
B side storage flag' (Un\G475)
digit: Digital output value
t: Time
T
: Conversion cycle
1
T
: Inter-module synchronization cycle
2
Ld: Number of data that were logged within the inter-module synchronization cycle
●: Timing of A/D conversion
1 FUNCTIONS
110
1.15 Continuous Logging Function
digit
T
2
T
T
T
T
T
T
T
1
1
1
1
1
1
Synchronous conversion value
Start (1)
Continuous logging in process (2)
Storing
N
Logging data storage in
A side not completed (0)
The flag is set by 5000 points.
T
2
T
T
T
T
T
T
T
1
1
1
1
1
1
1
1
Synchronous conversion value
Storing
N+Ld
N+(Ld×2)
Logging data storage in A side completed (1)
Logging data storage in B side not completed (0)
T
2
Synchronous conversion value
Stop (0)
Continuous logging start request waiting (1)
Logging stopped
Storing
N+(Ld×3)
t
Synchronous conversion value