Mitsubishi Electric MELSEC iQ-R User Manual page 163

High speed analog-digital converter module
Hide thumbs Also See for MELSEC iQ-R:
Table of Contents

Advertisement

Error code
Error name
197H
High pass filter setting range
error
Description and cause
A value out of the range is set in CH HPF Pass
band edge frequency or CH Attenuation band
width.
Action
Set CH HPF Pass band edge frequency and CH
Attenuation band width to the following values:
■When the conversion cycle is 10s
• Pass band edge frequency - Attenuation band
width > 0
• Attenuation band width  1300
• Pass band edge frequency  48000
■When the conversion cycle is 20s
• Pass band edge frequency - Attenuation band
width > 0
• Attenuation band width  650
• Pass band edge frequency  24000
■When the conversion cycle is 30s
• Pass band edge frequency - Attenuation band
width > 0
• Attenuation band width  440
• Pass band edge frequency  16000
■When the conversion cycle is 40s
• Pass band edge frequency - Attenuation band
width > 0
• Attenuation band width  330
• Pass band edge frequency  12000
■When the conversion cycle is 60s
• Pass band edge frequency - Attenuation band
width > 0
• Attenuation band width  220
• Pass band edge frequency  8000
■When the conversion cycle is 80s
• Pass band edge frequency - Attenuation band
width > 0
• Attenuation band width  170
• Pass band edge frequency  6000