• When performing the offset/gain setting, set the module as a synchronization non-target, and switch the mode to the
normal mode (medium speed: 10s/CH) or normal mode (low speed: 20s/CH), and then switch the mode again to the
offset/gain setting mode.
• Dedicated instructions cannot be used. The following shows the operation when a dedicated instruction has been
executed.
Dedicated instruction
G(P).OFFGAN
G(P).OGLOAD
G(P).OGSTOR
*1 For details on the dedicated instructions, refer to the following.
 MELSEC iQ-R Programming Manual (Instructions, Standard Functions/Function Blocks)
1 FUNCTIONS
134
1.18 Inter-Module Synchronization Function
*1
Operation
If the G(P).OFFGAN instruction is executed, a mode switching request error (alarm code: 0D00H) occurs.
The G(P).OGLOAD instruction is disabled.
If the G(P).OGSTOR instruction is executed, a G(P).OGSTOR instruction execution error in offset/gain setting mode (error
code: 1860H) is stored in the dedicated instruction completion status.