Setting procedure
1.
Set "Warning output setting (Process alarm)" to "Enable".
[Navigation window] [Parameter] [Module Information] Module model name [Application setting] [Warning
output function (Process alarm)]
2.
Set values for "Process alarm upper upper limit value", "Process alarm upper lower limit value", "Process alarm lower
upper limit value", and "Process alarm lower lower limit value".
Item
Process alarm upper upper limit value
Process alarm upper lower limit value
Process alarm lower upper limit value
Process alarm lower lower limit value
Set values within the range satisfying the condition "Process alarm upper upper limit value Process alarm
upper lower limit value Process alarm lower upper limit value Process alarm lower lower limit value".
1 FUNCTIONS
54
1.11 Warning Output Function
Setting range
-32768 to 32767