Mitsubishi Electric MELSEC iQ-R User Manual page 51

High speed analog-digital converter module
Hide thumbs Also See for MELSEC iQ-R:
Table of Contents

Advertisement

■Operations of when 'Operating condition setting request' (Y9) is turned on and off
• During the difference conversion, even when 'Operating condition setting request' (Y9) is turned on and off, the difference
conversion continues without updating the difference conversion reference value. To update the difference conversion
reference value, restart the difference conversion by changing 'CH1 Difference conversion trigger' (Un\G470) from Trigger
request (1) to No request (0), and Trigger request (1) again.
• Difference conversion trigger is not enabled even though the trigger changes from No request (0) to Trigger request (1)
while 'Operating condition setting request' (Y9) is on. After turning on and off 'Operating condition setting request' (Y9),
change 'CH1 Difference conversion trigger' (Un\G470) from No request (0) to Trigger request (1) again.
'Operating condition setting
request' (Y9)
'Operating condition setting
completed flag' (X9)
'CH1 Difference conversion
trigger' (Un\G470)
CH1 Digital operation value
before difference conversion
'CH1 Difference conversion
reference value' (Un\G432)
'CH1 Digital operation value'
(Un\G402)
'CH1 Difference conversion
status flag' (Un\G408)
■Operations of Maximum value and Minimum value
Once the difference conversion is started, the maximum value and the minimum value of the values acquired by the difference
conversion are stored in 'CH1 Maximum value' (Un\G404) and 'CH1 Minimum value' (Un\G406). By turning on 'Maximum
value/minimum value reset request' (YD), the maximum value and the minimum value after the start of the difference
conversion can be checked. When 'Maximum value/minimum value reset request' (YD) is not turned on, the maximum values
and minimum values before and after the difference conversion are mixed.
'CH1 Difference conversion
No request (0)
trigger' (Un\G470)
CH1 Digital operation value
before difference conversion
'CH1 Difference conversion
reference value' (Un\G432)
'CH1 Digital operation value'
(Un\G402)
'CH1 Difference conversion
Not converted (0)
status flag' (Un\G408)
'CH1 Maximum value'
(Un\G404)
'CH1 Minimum value'
(Un\G406)
'Maximum value/minimum
value reset request' (YD)
'Maximum value/minimum
value reset completed flag' (XD)
ON
OFF
ON
OFF
Trigger request (1)
9950
10001 10100 10010 10510 12000 12100 13250
10000
10000 10000 10000 10000 10000 10000 10000
Not updated
-50
1
100
10
510
Converting difference (1)
9950
10001 10000 10210 10510 12000 12100 13250
0
0
10000 10000 10000 10000 10000 10000
9950
10001
0
210
510
Maximum value/minimum value before
difference conversion start
10001
10001 10001 10001 10001 10001 2100 3250
600
600
0
0
0
No request
Trigger request (1)
(0)
13000
13310
Updated
13000
13000
2000 12100 13250
0
310
Not
Converting difference
converted
(1)
(0)
Trigger request (1)
9950
10100
10000
10000
2000
2100
3250
-50
100
Converting difference (1)
Maximum value/minimum value after
difference conversion start
3250
3250
0
2100
2100
-50
-50
ON
OFF
ON
OFF
1 FUNCTIONS
1.9 Difference Conversion Function