• To apply the offset/gain values set in one module to the other modules in the same system:
Ex.
When the offset/gain values in module No.1 are applied to modules No.2 to No.4
Saving and restoring with dedicated instructions
Use the dedicated instruction G(P).OGLOAD to temporarily save the offset/gain values of the source A/D converter module to
the internal device of the CPU module, and use the G(P).OGSTOR to write the values to the destination A/D converter
module.
Prevent the saved offset/gain setting data from being deleted, by one of the following methods before replacing the modules:
• Use latch settings for the internal device of the destination module.
• Save the data onto an SD memory card. (To write data: use the SP.FWRITE instruction. To read data: use the SP.FREAD
instruction.)
• Store the saved data.
For how to use dedicated instructions, refer to the following.
 MELSEC iQ-R Programming Manual (Instructions, Standard Functions/Function Blocks)
1.
Save the offset/gain values of module No.1.
2.
Apply the offset/gain values to modules No.2 to No.4.
1.21 Backing up, Saving, and Restoring Offset/Gain Values