■Response time
Response time is the time taken to obtain an attenuation characteristic (-53(dB)) after filter processing is started. The following
figure shows the response time.
Ex.
The output waveform obtained after an input SIN wave passed through a digital filter.
A
(1)
0
0
A
(2)
0
(5)
0
(3)
(4)
A: Amplitude
t: Time (ms)
(1) Input waveform
(2) Waveform after the digital filtering
(3) Start of the filter processing
(4) Timing to obtain an attenuation characteristic
(5) Response time (Conversion cycle Filter degree
*1 The filter degree is calculated with the following formula.
= 3.3 Sampling frequency Attenuation band width
= 3.3 (1000000 Sampling cycle) Attenuation band width (Value after the decimal point is rounded up.)
When the calculation result of the formula above is an even value, add 1 to the value so that it becomes an odd value.
t
t
*1
)
1 FUNCTIONS
1.5 A/D Conversion Method
1
37