Mitsubishi Electric MELSEC iQ-R User Manual page 242

High speed analog-digital converter module
Hide thumbs Also See for MELSEC iQ-R:
Table of Contents

Advertisement

CH1 User range setting offset/gain value
Medium speed
This area restores the offset/gain setting value in the user range setting.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Factory default setting offset value (L)
CH Factory default setting offset value (H)
CH Factory default setting gain value (L)
CH Factory default setting gain value (H)
CH User range setting offset value (L)
CH User range setting offset value (H)
CH User range setting gain value (L)
CH User range setting gain value (H)
When the following operations are performed, the data to be used is stored (saved).
• Writing the initial setting with an engineering tool
• Turning on 'Operating condition setting request' (Y9) (Data is not saved when the mode is switched from the normal mode
to the offset/gain setting mode by 'Mode switching setting' (Un\G296, Un\G297).)
• Writing an offset/gain value in the offset/gain setting mode (When 'User range write request' (YA) is turned on)
When restoring the offset/gain setting value in the user range setting, set the same data as the saved data in this area to the
corresponding area of the A/D converter module that is the restoration destination.
For the offset/gain setting, refer to the following.
 MELSEC iQ-R High Speed Analog-Digital Converter Module User's Manual (Startup)
■Default value
The default value is 0 for all channels.
APPX
240
Appendix 3 Buffer Memory Areas
Low speed
CH1
CH2
4004
4008
4005
4009
4006
4010
4007
4011
4020
4024
4021
4025
4022
4026
4023
4027
CH3
CH4
4012
4016
4013
4017
4014
4018
4015
4019
4028
4032
4029
4033
4030
4034
4031
4035