Referencing (Only For Absolute Encoder); Pto Function - Siemens SINAMICS V90 Operating Instructions Manual

Hide thumbs Also See for SINAMICS V90:
Table of Contents

Advertisement

Control functions
7.3 Pulse train input position control (PTI)
Note
When you use the CLR high level to clear the pulses (p29242 = 1), the high level need to be
kept for more than 8 ms.
When the signal CLR is active in the PTI mode or a compound mode with PTI, the alarm
A7585 occurs.
If there are overshoot when you use the CLR function, you need to increase the integral time
(p29121).
7.3.11

Referencing (only for absolute encoder)

If an absolute encoder is used, you must adjust the absolute encoder with the BOP menu
function "ABS". For more information about the "ABS" menu function, see Section "Adjusting
an absolute encoder (Page 158)".
7.3.12

PTO function

Function
A pulse train encoder output (PTO) which provides pulse signals can transmit the signals to
the controller to realize a closed-loop control system inside the controller, or transmit them to
another drive as pulse train setpoint for a synchronous axis.
Electronic gear
The electronic gear ratio is a multiplier factor to the PTO to a controller. It is realized with a
numerator and a denominator. One numerator (p29031) and one denominator (p29032) are
used for the PTO electronic gear ratio:
180
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E36037884-002

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotics s-1fl6

Table of Contents