General information
2.7 Technical data
Parameter
condi-
tions
Ambient humidity
Operating environment
Altitude
Degree of protection
Degree of pollution
Vibration
Operation
Product packag-
ing
Certifica-
tions
When SINAMICS V90 works with a motor with a brake, the voltage tolerance of 24 VDC power supply must be -10% to
1 )
+10% to meet the voltage requirement of the brake.
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be
2)
provided in accordance with the National Electrical Code and any additional local codes.
The V90 200 V servo drive has an overvoltage threshold of 410 VDC and an undervoltage threshold of 150 VDC; the
3)
V90 400 V servo drive has an overvoltage threshold of 820 VDC and an undervoltage threshold of 320 VDC.
SINAMICS V90 does not support motor overtemperature protection. Motor overtemperature is calculated by I
4)
protected by the output current from the drive.
48
Description
Storage
-40 °C to +70 °C
Operation
< 90% (non-condensing)
Storage
90% (non-condensing)
Indoors (without direct sunlight), free from corrosive gas, combustible gas, oil
gas, or dust
≤ 1000 m (without power derating)
IP 20
Class 2
Shock
Operational area II
Peak acceleration: 5 g, 30 ms and 15 g, 11 ms
Quantity of shocks: 3 per direction × 6 directions
Duration of shock: 1 s
Vibration
Operational area II
10 Hz to 58 Hz: 0.075 mm deflection
58 Hz to 200 Hz: 1 g vibration
Vibration
2 Hz to 9 Hz: 3.5 mm deflection
9 Hz to 200 Hz: 1 g vibration
Quantity of cycles: 10 per axis
Sweep seed: 1 octave/min
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E36037884-002