Bit
Signals
2
OFF3
1: No OFF3 (enable is possible)
0: OFF3 (fast braking then pulse cancela-
tion and power on inhibit)
3
OPER
1: Enable operation (pulses can be ena-
bled)
0: Inhibit operation (cancel pulses)
4
Reserved
-
5
Reserved
-
6
Reserved
-
7
RESET
Reset faults
8
Reserved
-
9
Reserved
-
10
PLC
Enable master control from the PLC
11
Reserved
-
12
Reserved
-
13
Reserved
-
14
Reserved
-
15
Reserved
-
Bit
Signals
0
SON_OFF1 Rising edge to enable SON (pulses can
be enabled).
0: OFF1 (braking with ramp-function
generator, then pulse cancellation, ready
to power up)
1
OFF2
1: No OFF2 (enable is possible)
0: OFF2 (immediate pulse cancelation
and power on inhibit)
2
OFF3
1: no OFF3 (enable is possible)
0: OFF3 (fast braking then pulse cancela-
tion and power on inhibit)
3
OPER
1: Enable operation (pulses can be ena-
bled)
0: Inhibit operation (cancel pulses)
4
EN_RAMP
1: Operating condition (the ramp function
generator can be enabled)
0: Inhibit ramp function generator (set the
ramp function generator output to zero)
5
Reserved
-
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E36037884-002
PTI control mode
Description
S control mode
Description
7.7 Communicating with the PLC
IPos control mode
Signals
OFF3
1: No OFF3 (enable is possible)
0: OFF3 (fast braking then pulse cancela-
tion and power on inhibit)
OPER
1: Enable operation (pulses can be ena-
bled)
0: Inhibit operation (cancel pulses)
SETP_ACC Rising edge to accept MDI setpoint
TRANS_TY
1: Accept new setpoint immediately
PE SE
0: Accept on rising edge of SETP_ACC
POS_TYP
1: Absolute positioning
0: Relative positioning
RESET
Reset faults
Reserved
-
Reserved
-
PLC
Enable master control from the PLC
Reserved
-
Reserved
-
SREF
Start referencing (act as REF for refer-
ence mode 0)
Reserved
-
Reserved
-
T control mode
Signals
SON_OFF1 Rising edge to enable SON (pulses can
be enabled).
OFF2
1: No OFF2 (enable is possible)
0: OFF2 (immediate pulse cancelation
and power on inhibit)
OFF3
1: no OFF3 (enable is possible)
0: OFF3 (fast braking then pulse cancela-
tion and power on inhibit)
OPER
1: Enable operation (pulses can be ena-
bled)
0: Inhibit operation (cancel pulses)
Reserved
-
Reserved
-
Control functions
Description
Description