Diagnostics
11.2 List of faults and alarms
Fault
F1018: Booting has been
interrupted several times
Reaction: NONE
Acknowledgement: POWER
ON
F1030: Sign-of-life failure for
master control
Reaction: OFF3
Acknowledgement:
IMMEDIATELY
F1611: SI CU: Defect detect-
ed
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F1910: Fieldbus: setpoint
timeout
Reaction: OFF3
Acknowledgement:
IMMEDIATELY
F7011: Motor overtempera-
ture
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F7085: Open-loop/closed-
loop control parameters
changed
Reaction: NONE
Acknowledgement:
IMMEDIATELY
330
Cause
Module booting was interrupted several
times. As a consequence, the module
boots with the factory setting.
Possible reasons for booting being inter-
rupted:
Power supply interrupted.
CPU crashed.
Parameterization invalid.
After this fault is output, then the module is
booted with the factory settings.
For active PC master control, no sign-of-
life was received within the monitoring
time.
The drive-integrated "Safety Integrated"
(SI) function on the Control Unit (CU) has
detected an error and initiated an STO
The reception of setpoints from the
fieldbus interface (Modbus/USS) has been
interrupted.
Bus connection interrupted.
Controller switched off.
Controller set into the STOP state.
Motor overloaded
Motor surrounding temperature too
high
Wire breakage or sensor not connected
Motor temperature model incorrectly
parameterized
Open-loop/closed-loop control parameters
have had to be changed for the following
reasons:
As a result of other parameters, they
have exceeded the dynamic limits.
They cannot be used due to the fact
that the hardware detected not having
certain features.
Remedy
Carry out a POWER ON (power off/on).
After switching on, the module reboots
from the valid parameterization (if availa-
ble).
Restore the valid parameterization
Examples:
Carry out a first commissioning, save,
carry out a POWER ON (switch-off/switch-
on).
Load another valid parameter backup
(e.g. from the memory card), save, carry
out a POWER ON (switch-off/switch-on).
Note:
If the fault situation is repeated, this fault is
again output after several interrupted boots.
Contact the Hotline.
Carry out a POWER ON (power off/on) for
all components.
Upgrade software.
Replace the Control Unit.
Restore the bus connection and set the con-
troller to RUN.
Reduce the motor load.
Check the surrounding temperature and
the motor ventilation.
Check the wiring and the connection.
Check the motor temperature model pa-
rameters.
It is not necessary to change the parameters
as they have already been correctly limited.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E36037884-002