Description
Write the control word via PLC.
Write the setpoint and read the status word via PLC.
Example 1
This example shows the operating procedures when we use the setpoint and control word
from Modbus (p29008 = 1) as the Modbus control source in S control mode.
1.
2.
3.
4.
5.
6.
7.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E36037884-002
Set RS485 bus address for the drive.
• p29004 = 1
Select the Modbus protocol by p29007.
• p29007 = 2
Select Modbus control source by p29008.
• p29008 = 1
Set the transmission baud rate by p29009.
• p29009 = 8 (38400 baud)
Set the drive work mode to S control mode.
Save the parameters and restart the drive.
Configure the PLC parameters.
Note:
Keep the PLC baud rate the same as the drive setting.
Set even parity check for the PLC (parity = 2).
Note:
Bit 10 of the register 40100 must be set to 1 to allow the PLC
to control the drive.
You need to trigger a rise edge for OFF1 to enable SON sta-
tus for the motor, and OFF2 and OFF3 must be set to 1. The
step must be executed when you enable SON for the first
time.