Siemens SINAMICS V90 Operating Instructions Manual page 223

Hide thumbs Also See for SINAMICS V90:
Table of Contents

Advertisement

Definition of register 40110
Bit
Signals
0
RDY
1
FAULT
2
INP
3
ZSP
4
SPDR
5
TLR
6
SPLR
7
MBR
8
OLL
9
WARNING 1
10
WARNING 2
11
REFOK
12
MODE 2
13
Reserved
14
Reserved
15
Reserved
DI simulation
The digital input signals can be simulated by Modbus with registers 40281 and 40283.
Digital input
Register
40281 (p0795)
Register
40283 (p0796)
● Set the simulation mode for DIs with register 40281
Bit 0 to bit 9 of register 40281 can be used to set the simulation mode for DI1 to DI 10.
For example, if you want to simulate DI1 with Modbus, you need to set bit 0 = 1 for
register 40281.
● Set the setpoint for DIs with register 40283
Bit 0 to bit 9 of register 40283 can be used to set the setpoint for the simulated DI signals.
After the DI simulation mode is set, you can set the setpoint for a DI signal with register
40283 to enable the DI signal. For example, if you have set bit 0 = 1 for register 40281, to
enable signal DI1, you need to set the trigger condition (rising edge or high level) for bit 0
of register 40283.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E36037884-002
PTI, IPos, S and T control modes
Servo ready
Fault status
In-position signal
Zero speed detection
Speed reached
Torque limit reached
Speed limit reached
Motor holding brake
Overload level reached
Warning 1 condition reached
Warning 2 condition reached
Referenced
In the second control mode
-
-
-
DI1
DI2
DI3
Bit 0
Bit 1
Bit 2
Bit 0
Bit 1
Bit 2
7.7 Communicating with the PLC
Description
DI4
DI5
DI6
Bit 3
Bit 4
Bit 5
Bit 3
Bit 4
Bit 5
Control functions
DI7
DI8
DI9
Bit 6
Bit 7
Bit 8
Bit 6
Bit 7
Bit 8
DI10
Bit 9
Bit 9
223