Siemens SINAMICS V90 Operating Instructions Manual page 80

Hide thumbs Also See for SINAMICS V90:
Table of Contents

Advertisement

Connecting
4.1 System connection
Danger to life when PE connectors are touched
When the equipment is working, hazardous touch current can be present at the PE
connectors; if touched, this can result in death or severe personal injury.
• Do not touch the PE connector during operation or within a certain period since power
Personal injury and damage to property from improper connections
Improper connections have high risks of electrical shock and short circuit, which will
jeopardize personal safety and equipment.
• The drive must be directly connected with the motor. It is not permissible to connect a
• The line supply voltage must be within the allowable range (refer to the drive rating
• Never wire up the U, V, W terminals in an interchanged phase sequence.
• If the CE marking for cables is mandatory in some cases, the motor power cable, line
• For terminal box connection, make sure that the clearances in air between non-insulated
• Route signal cables and power cables separately in different cable conduits. The signal
• Cables connected may not come into contact with rotating mechanical parts.
NOTICE
Important wiring information
In order to meet EMC requirements, all cables must be shielded cables.
The cable shields of shielded twisted-pair cables should be connected to the shielding plate
or the hose clamp of the servo drive.
NOTICE
Drive damage caused by short-circuiting between the shielding wire and the unused pin on
the setpoint connector
The shielding wire may inadvertently be short-circuited to the unused pin on the to-be-
assembled setpoint connector. This can cause damage to the drive.
Exercise caution when connecting the shielding cable to the setpoint connector.
You can see the assembly method of encoder connector in Section "Assembly of cable
terminals on the drive side (Page 349)" for reference.
80
DANGER
disconnection.
WARNING
capacitor, inductor or filter between them.
plate). Never connect the line supply cable to the motor terminals U, V, W or connect
the motor power cable to the line input terminals L1, L2, L3.
supply cable and brake cable used must all be shielded cables.
live parts are at least 5.5 mm.
cables shall be at least 10 cm away from the power cables.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E36037884-002