7.2.8
Set date
Set date and time.
& time
7.2.9
Automatic switching
Summer/
winter time
7.2.10
V1 time
Manned/
unmanned
V2 time
Automatic switch to
unmanned
Switching time
7.2.11
The service information is shown in quiescent mode. Insert text as per chapter 7.5,
Service
information
e.g. FC12x 'address and telephone number'.
7.2.12
On: Enable the panel's internal buzzer. à Comply with EN 54-2
Buzzer
Off: Disable the panel's internal buzzer. à Not comply with EN 54-2
7.2.13
Calibration for all programmed supervision outputs at once.
Calibrate
line
Line calibration is needed to achieve supervision. As a result of the calibration, the line
resistance is indicated and can be provided using your own calculation.
Smart Infrastructure
Set date and time
Summer / winter time
If selected, the panel will switch automatically to the summer /
winter time each year.
Manned / unmanned
Select the reaction time V1, value from 30 sec. - 4 min.
Select the investigation time V2, value from 1 min. - 10 min.
Allowed time with regards to EN 54-2 is V1+V2 = 10 min.
Enable the daily switching time.
Set the switching time to unmanned.
Service information
Buzzer
Calibrate line
61