Section 13
Logic
13.9.2
13.9.3
13.9.4
502
Functionality
Elapsed Time Integrator (TEIGGIO) function is a function that accumulates the elapsed
time when a given binary signal has been high.
The main features of TEIGGIO are
•
Applicable to long time integration (≤999 999.9 seconds).
•
Supervision of limit transgression conditions and overflow.
•
Possibility defining a warning or alarm with the resolution of 10 milliseconds.
•
Retain the integration value at a warning/alarm/overflow.
•
Possibilities for blocking and reset.
•
Report the integrated time
Function block
TEIGGIO
BLOCK
WARNING
IN
ALARM
RESET
OVERFLOW
ACCTIME
IEC13000005-1-en.vsd
IEC13000005 V1 EN
Figure 233:
TEIGGIO function block
Signals
Table 341:
TEIGGIO Input signals
Name
Type
BLOCK
BOOLEAN
IN
BOOLEAN
RESET
BOOLEAN
Default
Description
0
Freeze the integration and block the other outputs
0
The input signal that is used to measure the elapsed
time, when its value is high
0
Reset the integration time
1MRK 502 048-UUS A
Technical manual