Signals - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
8.9.4
8.9.5
Table 143:
NS2PTOC (46I2) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
tAlarm
0.00 - 6000.00
OpStep1
Disabled
Enabled
I2-1>
3 - 500
CurveType1
Definite
Inverse
t1
0.00 - 6000.00
tResetDef1
0.000 - 60.000
Table continues on next page
Technical manual

Signals

Table 141:
NS2PTOC (46I2) Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLK1
BOOLEAN
BLK2
BOOLEAN
Table 142:
NS2PTOC (46I2) Output signals
Name
Type
TRIP
BOOLEAN
TRST1
BOOLEAN
TRST2
BOOLEAN
PICKUP
BOOLEAN
PU_ST1
BOOLEAN
PU_ST2
BOOLEAN
ALARM
BOOLEAN
NSCURR
REAL
Settings
Unit
Step
-
-
s
0.01
-
-
%IB
1
-
-
s
0.01
s
0.001
Default
Description
-
Group connection for neg seq.
0
Block of function
0
Block of step 1
0
Block of step 2
Description
Common trip signal
Trip signal for step 1
Trip sognal for step 2
Common start signal
Pickup signal for step 1
Pickup signal for step2
Alarm signal
Negative sequence current in primary amps
Default
Description
Disabled
Disable/Enable Operation
3.00
Time delay for alarm ( operated by pick up
signal) in seconds
Enabled
Enable execution of step 1
10
Step 1 Neg. Seq. Current pickup level, in % of
IBase
Definite
Selection of definite or inverse time-characteri.
for step 1
10.00
Definite time delay for trip of step 1, in sec
0.000
Time delay for reset of definite timer of step 1,
in sec