Section 14
Monitoring
Table 368:
VMSQI Non group settings (advanced)
Name
Values (Range)
3V0ZeroDb
0 - 100000
3V0HiHiLim
0 - 2000000
3V0HiLim
0 - 2000000
3V0LowLim
0 - 2000000
3V0LowLowLim
0 - 2000000
V1ZeroDb
0 - 100000
V1HiHiLim
0 - 2000000
V1HiLim
0 - 2000000
V1LowLim
0 - 2000000
V1LowLowLim
0 - 2000000
V1LimHys
0.000 - 100.000
V2ZeroDb
0 - 100000
V2HiHiLim
0 - 2000000
V2HiLim
0 - 2000000
V2LowLim
0 - 2000000
V2LowLowLim
0 - 2000000
14.1.6.5
524
Unit
Step
m%
1
V
1
V
1
V
1
V
1
m%
1
V
1
V
1
V
1
V
1
%
0.001
m%
1
V
1
V
1
V
1
V
1

Monitored data

Table 369:
VMSQI Monitored data
Name
Type
3V0
REAL
3V0ANGL
REAL
V1
REAL
V1ANGL
REAL
V2
REAL
V2ANGL
REAL
Default
Description
500
Zero point clamping
288000
High High limit (physical value)
258000
High limit (physical value)
213000
Low limit (physical value)
198000
Low Low limit (physical value)
500
Zero point clamping
96000
High High limit (physical value)
86000
High limit (physical value)
71000
Low limit (physical value)
66000
Low Low limit (physical value)
5.000
Hysteresis value in % of range and is common
for all limits
500
Zero point clamping
96000
High High limit (physical value)
86000
High limit (physical value)
71000
Low limit (physical value)
66000
Low Low limit (physical value)
Values (Range)
Unit
-
kV
-
deg
-
kV
-
deg
-
kV
-
deg
1MRK 502 048-UUS A
Description
3U0 Amplitude
3U0 Angle
U1 Amplitude
U1 Angle
U2 Amplitude
U2 Angle